Power cable installation considerations

1. The distance between the cable and the heat pipe should be 2m when installed in parallel, and 0.5m when crossing.

2. When the cable is installed parallel or crosswise to other pipes, it must maintain a distance of 0.5m.

3. When the cable is directly buried and installed, the depth of direct burial of the 1-35kV cable shall not be less than 0.7m.

4. The mutual installation distance of 10kV and below cable shall be not less than 0.1m, 10-35kV shall not be less than 0.25m, and the distance shall not be less than 0.5m.

5, the minimum bending radius of the cable, multi-core cable shall not be less than 15D, single core cable shall not be less than 20D (D is the cable outer diameter).

6、6kV and above cable joints a、When installing the cable terminal, the semi-conductive shielding layer must be stripped off, and the insulation must not be damaged during operation. The condition of knife marks and unevenness should be avoided. If necessary, sandpaper should be used to flatten the shield; It should be flat and the graphite layer (carbon particles) should be removed.

b. The copper shield and steel pick at the end of plastic insulated cable must be well grounded. This principle should also be followed for the short circuit to avoid induction dynamics at the end of the steel crucible when the three-phase unbalanced operation is running, and even “fire” and burning protection. Sets and other accidents. The grounding lead wire should be tinned and galvanized with tinned copper and copper cable, and should not be sealed with a torch to avoid burning insulation.

c. The three-phase copper shields shall be connected to the ground wires respectively. Note that the shield grounding wire and the steel wire grounding wire shall be led out separately and insulated from each other. The position of the welding ground wire shall be as low as possible.

8, the basic requirements of the cable terminal and intermediate joints: a. good conductor connection; b insulation is reliable, recommended radiation cross-linked heat-shrinkable silicone rubber insulation material; c. sealed well; d. sufficient mechanical strength, Can adapt to various operating conditions.

7. The end of the cable must be waterproof, as well as the erosion of other corrosive materials to prevent breakdown caused by aging of the insulating layer caused by water trees.

9. Cranes and forklifts must be used for loading and unloading cables. It is forbidden to lay them flat and lay flat. Large cable installations must be used to prevent cable from being damaged by external forces or scratching the jacket and insulation layer due to manual dragging. The cable is not installed, it is strictly forbidden to use human hand to make the conductor bent to damage the insulation layer and produce a short circuit.

10. If the cable cannot be laid in time for any reason, it should be stored in a dry place to prevent sunlight exposure and water ingress at the end of the cable.

Note: The installation of wires and cables should be performed by an installer or a professional technician who is familiar with the performance of wires and cables. If there are still unclear matters, please consult the relevant technical department or the technical department of our company in time.

The statement that the download traffic is from the Internet is for reference only and the Others do not explain.

0.6/1KV copper-core PVC insulated power cable laid in air for long-term continuous load under load conditions

Spring

Lanejoy is all kinds of spring Manufacturer at china 10 years, we had made compression spring, Wire Spring, Torsion Spring, Tension Spring, recoil spring and so on.

we also can do for OEM OR ODM


compression spring,wire spring,torsion spring,tension spring,recoil spring

Shenzhen Lanejoy Technology Co.,LTD , https://www.wirefruitbasket.com

This entry was posted in on