Fire extinguisher's retirement period

[Introduction]

From the date of manufacture, the following years must be retired:

Portable chemical foam fire extinguisher - 5 years;

Portable acid and alkali fire extinguisher - 5 years;

Portable water fire extinguisher - 6 years;

Portable dry powder fire extinguisher (gas cylinder type) - 8 years;

Portable storage pressure dry powder fire extinguisher - 10 years;

Portable 1211 fire extinguisher - 10 years;

Portable carbon dioxide fire extinguisher - 12 years;

Trolley

Learning foam fire extinguisher - 8 years;

Trolley type dry powder fire extinguisher (gas cylinder type) - 10 years;

Trolley storage pressure dry powder fire extinguisher -- 12 years;

Trolley type 1211 fire extinguisher - 10 years;

Cart type carbon dioxide fire extinguisher - 12 years.

In addition, fire extinguishers or gas cylinders that should be scrapped must be perforated in the barrel or bottle, and the obvious signs of “retired” should be affixed with self-adhesive. The contents are as follows: “retired”, the font size is 25mm× 25mm; retirement year, month; name of maintenance unit; signature of inspector. Fire extinguishers should be inspected at least once a year.